Flexible Tag Maintenance using Static & Dynamic Tags, Bulk Creation, Import & Export

Important Notes:

  • It is highly recommended to configured at least one static tag with a valid device address under each of your devices.  This facilitates easier troubleshooting when using the included OPC Quick Client for communication testing.
  • Both static tags and dynamic tag addresses can be used at the same time from any client application.
  • For dynamic tag addresses:
    • If any data type other than the default data type (which is specified in each driver help file for supported addresses) is required, TOP Server supports appending an "@" symbol to the end of the address followed by the desired data type (for instance, a Modbus holding register of 400001 is a default data type of Word - if you wished to access 400001 as a Short, you would specify a dynamic tag address of 400001@short in your client application).  Consult the TOP Server help file under Basic Server Components -> What is a Tag? -> Dynamic Tags for more details.
    • TOP Server also supports overriding the update rate on a per tag basis for non-OPC clients by appending an "@" symbol to the end of the dynamic tag address followed by the desired update rate in milliseconds (ms).
  • If a dynamic tag address is used in a client and that address matches the name of a static tag already defined in the server, the address referenced by the static tag overrides the dynamic address reference.
  • Static tags must be used to scale data in the server (i.e. scaling data is not possible using dynamic tag addressing).