TOP Server Fisher ROC Serial Overview
EFM SupportROC Protocol

TOP Server Fisher ROC Serial OPC Driver

High performance real-time and EFM retrieval for ROC serial devices

4.7(89 reviews)

Available in Driver Suites

This driver is available in the following TOP Server driver suites:

1,024

Max Channels

255

Devices per Channel

Protocol

Remote Operation Controllers (ROC)

Networks

Serial RS-232, RS-422, RS-485; Ethernet Encapsulation

Product Overview

The Fisher ROC Serial Device Driver works in conjunction with TOP Server® to provide data exchange between OPC, SuiteLink and DDE clients and Emerson Fisher ROC devices supporting the ROC protocol over serial or Ethernet encapsulation. This includes FloBoss, RegFlo and ROC 300 Series devices. No tag count limits or limits on the number of connected clients.

When part of the TOP Server EFM Suite, the Fisher ROC Serial driver also collects historical Electronic Flow Measurement (EFM) gas history data via the EFM Exporter plug-in, supporting export formats including Flow-Cal, PGAS and more. Such data is commonly used for production optimization and regulatory compliance.

Why Choose This Driver?

Proven benefits that help you deploy faster and operate more reliably

Ethernet Encapsulation Support

Supports Ethernet Encapsulation via Ethernet/Serial convertors, Ethernet Device or Terminal servers

Automatic Tag Generation

Supports Automatic Tag Generation

Operator Identification

Operator Identification (including configurable Access Level)

Synchronization

Time Synchronization

Modem

Modem Support

TOP Server Built-In Features

Multi-threaded architecture for high scalability, Runtime changes via wizard-based configuration interface with intuitive Properties Editor, Secure User Management, Built-in Device/Network Redundancy, Auto-Demotion (Slow Polling), Extensive communication and server diagnostics (OPC / Communications / Event Log)

EFM Support

EFM Support using the EFM Exporter Plug-In (EFM Suite Only): FlowCal CFX (V5), FlowCal Transaction Queue, PGAS, CSV, SQL / ODBC Databases

History, Alarms & Events

Support for hourly history, daily history, alarms, and events

Cache Management

Enable/Disable Clearing Cache on Next Upload

EFM Configuration & Mapping

EFM Configuration and Mapping (EFM History / EFM Alarm / EFM Event)

EFM Pointer File Caching

EFM Pointer File caching to disk (eliminates repoll when server is restarted)

Pointer Rollback

Pointer Rollback capability for retrieving lost EFM data from a device

EFM Poll Time Synchronization

Time synchronization on EFM poll, user-specified interval, or time of day

Configurable History Timestamp

FloBoss 107 Only - Configurable for trailing or leading history timestamp

NOTE:

The meter order in the EFM meter list in the driver MUST match the meter order in ROCLink800 configuration software.

"Fast response. Software Toolbox had my activation IDs sent to me in minutes, and I was able to move forward!"

Automation Engineer

Hilcorp Energy Company

Key Features & Benefits

Everything you need for reliable industrial connectivity

Channel & Device Capacity

Channels – 1,024; Devices per Channel – 255 for highly scalable ROC serial deployments.

EFM Gas Retrieval

Support for Gas Electronic Flow Measurement (EFM) retrieval for production optimization and regulatory compliance.

User Program Data Access

Read, Write, and Auto Tag Generation of User Program Data (User Defined Points)

OpCode 10 & 11 Support

Supports OpCodes 10 and 11 for reading and writing to user tables

Configurable OpCode for Read Requests

Configurable OpCode for Read RequestsOpCode 167 (Default) for reading entire point type logical addresses in one transaction, OpCode 180 for use if only a few parameters from each point type and logical address are required

Advanced Statistics Tags

Supports Advanced Statistics Tags, including _CommFailures, _ErrorResponses, and more

VCone Meter Support

Supports the VCone meter type and calculation method

Optimized Communication

Optimized for extreme conditions (noisy communication channels and low-bandwidth)

Technical Specifications

Protocol

Remote Operation Controllers (ROC)

Networks

Serial RS-232, RS-422, RS-485; Ethernet Encapsulation

Max Channels

1,024

Devices per Channel

255

License Type

Perpetual

Supported Devices

  • FloBoss 100 Series
  • FloBoss 407
  • FloBoss 500 Series
  • RegFlo
  • ROC 300 Series - FlashPAC
  • ROC 300 Series - ROCPAC

Note: For full details on models and networks supported, please consult the driver help file.