%20OPC%20Driver/TOP%20Server%20Siemens%20S7%20MPI%20(Multi%20Point%20Interface)%20OPC%20Driver%2000.jpg)
Reliable MPI Connectivity for Siemens S7-300 and S7-400 Controllers via RS-232 to MPI Adapter
This driver is only available as part of the following TOP Server driver suites:
Max Channels
Devices per Channel
Station Range
I, E, Q, A, M, F, T, C, Z, Data Block Access
The Siemens S7 MPI driver works in conjunction with TOP Server® to provide data exchange between OPC UA, OPC DA, SuiteLink and DDE clients and Siemens S7-300 and S7-400 controllers via the Siemens MPI (Multi Point Interface) protocol.
This driver communicates directly with the Siemens S7 MPI serial port adapter and provides extensive error handling to ensure data integrity. No additional software packages or libraries are required - just an RS-232 to MPI adapter and TOP Server.
Important Notes:
Proven benefits for reliable MPI connectivity to legacy Siemens S7-300 and S7-400 PLCs
Automatic Tag Database Generation using CSV Import
Tag configuration supports dynamic tags from your client application
Supports Stations 0-126
Memory Types Supported: I, E, Q, A, M, F, T, C, Z, and Data Block Access
Supports all memory types and data types such as Float, Long Word, and BCD
Bit-level access support
Supports arrays for byte, char, word, short, DWORD, long, float and LBCD data types
Supports Single or Multiple Masters on MPI network
Auto Device Demotion Support to optimize communication with responsive devices
Communicates directly with MPI Adapter (No Additional Software Required)
"The people in charge of assistance are responsive, the answers are precise and the contact is very pleasant."
Franck Feneon
Controls Engineer
Everything you need for reliable Siemens S7-300 and S7-400 MPI connectivity
Maximum Number of Channels & Devices: Channels - 100, Devices per Channel - 127, NOTE: Practical channel/device limits will vary depending on your available system resources
Supports all data types
Supports automatic handling of network configuration
Supports Multiple Master Multi-drop RS485 (19.2 KBaud and 38.4 KBaud)
Modem Support (Automatic Dial Configuration and Multiple Phone Number Management)
Supports Ethernet Encapsulation
Communicates directly with the Siemens MPI adapter - no additional Siemens software packages or libraries required.
Full bit-level access support for granular control and monitoring across all supported memory types.
Primary Protocol
Multi Point Interface (MPI) S7-300/400 Communications Protocol
Network Type
Multi-Master Multi-Drop
Serial Network
RS-485 Multi-drop (MPI network) at 19.2 kBaud and 38.4 kBaud
RS-232 Connection
RS-232 connection to an MPI adapter (adapter required; not included)
Modem Support
Dial-up with automatic dial configuration and multiple phone number management
Ethernet Encapsulation
Serial over Ethernet via terminal server
Max Channels
100
Devices per Channel
127
Station Range
0-126
Memory Types
I, E, Q, A, M, F, T, C, Z, Data Block Access
Data Types
Float, Long Word, BCD, byte, char, word, short, DWORD, long, LBCD
Client Interfaces
OPC UA, OPC DA, AVEVA SuiteLink, DDE
Note: For full details on models and networks supported, please consult the driver help file.
Everything you need to get started, configure, and troubleshoot your driver
Watch step-by-step video tutorials covering installation and configuration
View →Get started quickly with TOP Server installation and initial configuration
View →Comprehensive troubleshooting guide for common TOP Server issues
View →Complete driver documentation including configuration instructions, MPI adapter connections, multi-drop operation requirements, Ethernet Encapsulation support, and addressing syntax (Version 1.037)
Download →When using Dynamic Tags and reading/writing real (float) values, append '@float' to the end of the address. For non-default data types, use '@datatype' (Boolean, Byte, Char, Short, Word, Long, DWord, Float, BCD, LBCD, String)
View →CSV Import & Export Support for Static Tags - used for tag database generation via CSV import
View →View the complete TOP Server release history and version information
View →