I'm sure you've all at least had some interaction with Modbus, working in the automation industry. It's one of the most widely used protocols (if not the most widely used) in the world. Which is both its blessing and its curse, to some extent.
Given how long Modbus has been around and in use as an "open" protocol (starting in 1979), there have been many different interpretations of Modbus throughout the years. And with those different Modbus interpretations, much confusion about the different terminology for accessing data.
In this blog post, I will step through the basics of Modbus addressing including how offsets come into play, and how they affect what addresses to use in TOP Server for AVEVA applications.
Given the large number of Modbus protocol implementations in the world by almost as many different device manufacturers, device documentation can sometimes be unclear about what numerical address should be requested for a particular piece of data. So the intention of this post is to provide a somewhat standard explanation for how Modbus addressing works to make it easier to understand how to access the data in your Modbus devices using TOP Server.
When we discuss the Modbus protocol and how to address particular locations of data, there are generally four different types of Modbus addresses:
Since some device documentation does not provide a detailed listing of Modbus addresses containing references to the type of address such as 4xxxxx or Holding Register, it is useful to think of Modbus addresses in terms of the type of data a particular address will contain and whether or not it can be read from and written to or only read from.
You may also see registers referred to as analogs or coils referred to as discrete or digital addresses due to the type of data they represent.
As I've already mentioned, the Modbus protocol has been around for decades and is arguably the most widely used protocol for device communications in the world. That being said, with the birth of the Modbus protocol occurring when memory sizes were still relatively modest, the total amount of memory on a device in the late 70's was small compared to the large quantities of memory available today.
One of the most common questions asked when considering if the TOP Server Modbus Suite is compatible with a device is whether a particular address range is supported by TOP Server. The listed address ranges supported by TOP Server are as follows:
For many devices, the supported address ranges are much smaller than this. With holding registers, for example, in a device like this, an address of 4001 comes nowhere close to 400001 as a starting address. So how can TOP Server claim to have such wide support for Modbus devices given this data?
| Modbus Holding Register Addressing | |||
| Modbus Document Says: | TOP Server Says it Supports: | ||
| 4 | 001 | 4 | 00001 |
| 4 | 0001 | 4 | 00001 |
The TOP Server Modbus Suite does, in fact, support 4001, 40001 and even 400001. TOP Server effectively supports all Modbus addresses because Modbus uses a type of addressing referred to as offset addressing. Notice how, in the figure above, we have separated the starting number from the rest of the address. This is done to illustrate how an offset address works.
The address, “4001”, in the figure contains two pieces of information that we are interested in:
Given this knowledge, let’s apply the same principle to the starting Holding Register address supported by TOP Server, “400001”.
It is important to note that many Modbus devices may not support the full range of the data offsets that TOP Server supports. To avoid confusion when entering an address for such a device, TOP Server Modbus drivers "pad" the address (add a digit or digits) according to what was entered in the address field. As such, TOP Server automatically accounts for the “extra” zeroes in the middle and pads the address as needed.
This same principle is true for all of the different Modbus address types (Internal Register=3, Input Coil=1, Output Coil=0).
The reason this is true is because Modbus requests do not contain “400001” or “4001” when sent to the Modbus device when making a request. Only the address offset is sent as part of the command along with a function code that specifies a read or write operation and the type of Modbus address (Holding Register, etc.)
That being said, the easiest way to determine what address to use in the TOP Server is to determine what kind of address you are trying to access in the device:
View our related post for more specifics on Modbus Function Codes, and check out our TOP Server Modbus Addressing guide to view the above tips in a handy printable format.